Orion ISS
www.bolid.com 58
ISOLATED The detector or call point has not responded for more than 10 s
CONNECTED A response has been received from the addressable detector or call point
which was isolated before
Following is the list of available generalized statuses of alarm loops of the Type 14 displayable by a
S2000M console along with identifiers of the partition, the device, and the loop:
FIRE ALARM Two or more loop addressable zones have the Fire Alarm sta-
tus, or the Alarm Delay given for this loop has been expired
FIRE PREALARM There is at least one addressable zone in the Fire Alarm status
TROUBLE There is an addressable zone with the Trouble status, and there
is no zone with the Fire Alarm status
ISOLATED There is an isolated addressable zone in the loop, while there
are no zones with Fire Alarm or Trouble statuses
FIRE SIGNAL There is an addressable zone with Test status and there are no
zones with Isolated, Trouble, or Fire Prealarm, or Fire Alarm
statuses
ARM FAILED At the moment of arming, one of the addressable zones of the
loop has a not Norm status, no other zones having more priority
statuses (said above)
ARM DELAY The transient status when after an attempt to arm an addressa-
ble zone the response from the addressable detector is waiting
for, and there are no zones with more priority statuses (said
above)
SERVICE REQUIRED There is an addressable zone with the Dusty status, all other
zones being in Norm
DISARMED There is a disarmed addressable zone within the loop, all other
zones of the loop being armed
ARMED All addressable zones are in norm and armed