Signal-10 Operation Principles
27 www.bolid.com
zone is formed by adding the own detector or call point address (ranged from 1 to 10) to 10 times the
number of the loop incremented by one, so that:
Detectors connected to the contact LP1 are assigned to addressable zones 20-29
LP2 30-39
LP3 40-49
LP4 50-59
LP5 60-69
LP6 70-79
LP7 80-89
LP8 90-99
LP9 100-109
LP10 110-119
NOTE: No threshold addressable detectors or call points with the same own address can be
included into the same fire loop of the Type 14
The Signal-10 recognizes the following messages/conditions responded by addressable devices:
¾ Norm
¾ Dusty, Service Required
¾ Trouble
¾ Fire
¾ Manual Fire Alarm
¾ Test
¾ Isolated
A current condition of an alarm loop of the Type 14 is formed as a generalized condition of those ad-
dressable zones which are involved into this loop and matched with this loop by the given Related Ad-
dressable Detectors setting (see Alarm Loop Configuration Parameters section of this Manual). The
generalized condition of a loop of the Type 14 is defined as the most priority condition of all the ad-
dressable zones.
Following are all possible generalized conditions of a threshold addressable loop in the order of priority:
Fire Alarm Two or more loop addressable zones have the Fire Alarm sta-
tus, or the Alarm Delay given for this loop has been expired
Fire Prealarm There is at least one addressable zone in the Fire Alarm status
Trouble There is an addressable zone with the Trouble status, and there
is no zone with the Fire Alarm status
Isolated There is an isolated addressable zone in the loop, while there
are no zones with Fire Alarm or Trouble statuses