INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
44
The alarm loop entering into the “Armed”, “Disarmed”, “Aux Zone Re-
store” or any “Restore…” status, this status resolving time (recovery time)
is equal to the “Arming Delay” period.
The programmable auxiliary alarm loop status codes are enumerated
in Table 12.
Table 12: Programmable auxiliary loop status codes
Status
code
Status Message
1 AC power has been restored
AC POWER
RESTORE
2 AC power has been lost
AC POWER
FAILED
3 Intrusion alarm
INTRUSION
ALARM
17
Arming has failed due to the activated
status of detector
ARM FAILED
24
Detector status monitoring has been
switched on
ARMED
35 Auxiliary alarm loop has been restored
AUX ZONE
RESTORE
36 Auxiliary loop alarm AUX ZONE ALARM
37 Fire alarm FIRE ALARM
38
Zone disarmed. Arming is impossible due
to detector being in activated status
NOT READY TO
ARM
39 Extinguishing equipment is fault-free FIRE TRBL RST
41 Extinguishing equipment faults FIRE TROUBLE
44
Fire signal has been received and fire
alarm is probable
FIRE PREALARM
45 Open-circuit failure in the alarm loop LOOP TRBL OPEN
58 Silent zone alarm SILENT ALARM
71 The pressure or water level is falling LEVEL LOW
72
The pressure or water level is in normal
state
LEVEL NORMAL
74 The pressure or water level is rising LEVEL HIGH
75
The pressure or water level has ex-
ceeded the emergency threshold
LEVEL TOO HIGH
76
Temperature has exceeded the maxi-
mum value
TEMPERATURE
HIGH
77 The pressure or water level has fallen LEVEL TOO LOW