INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
26
If the device loops are assigned with the relays then control com-
mands via RS-485 interface will be ignored and the local relay control will
be in use. In such a manner the relay local control has priority over the
centralized control.
4.2.2 Relay centralized control
To control the relays by centralized commands via RS-485 interface:
- Set off the “Relay 1…5 Control” parameters for all the loops break-
ing the association between the loops and relays
- Give any executive program with the corresponding initial relay
status (switched on or off)
- Assign this relays with the corresponding partition in the net control-
ler configuration, define the executive program, give the control de-
lay and the control time
In case of relays being not assigned with the loops the “Relay Control
Program” parameter defines only the initial status of relay, that is, the
status which relay is set to after the power start up. Usually for relay to be
controlled on-line the programs with “turned off” initial statuses are used,
for example, the program 1 “Turn on”. After power starting up and until the
first centralized command switching the relay to the loops depending status
has been received some time can expire. So if the on-line executive pro-
gram supposing “turned on” initial status is in use then it is reasonable to
turn the relay on right after the power up. To do this it is necessary for the
device to give any executive program with “turned on” initial status, for ex-
ample, the program 2 “Turn off”.
4.2.3 The relay configuration parameters
Table 4: Relay configuration parameters
Parameter
name
Description Available range
Relay
Control
Program
Defines the relay control method de-
pending on the related loop statuses
and the initial relay status
0…37
Relay
Control
Time
The switching on or off period for the
executive programs with restricted
operating time
from 1 to 8192 s in
increments of 1/8 s
Circuit
Check
Type
Defines the outer circuit check
method for relay outputs "relay 4"
(К4) and "relay 5" (К5)
1 – without check
2 – open failure check
3 – short failure check
4 – both open and
short failure check